The consumer unit (cuadro eléctrico) is what separates a nuisance trip from a fire. In older Canarian apartments it is usually the weakest part of the whole installation.
Call +34 690 195 750| Device | Purpose |
|---|---|
| IGA (main switch) | Isolates the installation, sized to the electrification grade |
| Surge protection (SPD) | Protects electronics from transient overvoltage |
| RCDs 30 mA, type A where needed | Protect people; each covers at most five circuits |
| Circuit breakers (PIA) | One per circuit, sized to the cable (10 A / 16 A / 20 A / 25 A) |
| Labels | Every breaker named, in English and Spanish |
| Circuit | Use | Breaker | Cable |
|---|---|---|---|
| C1 | Lighting | 10 A | 1.5 mm² |
| C2 | General sockets | 16 A | 2.5 mm² |
| C3 | Cooker and oven | 25 A | 6 mm² |
| C4 | Washing machine, dishwasher, water heater | 20 A | 4 mm² |
| C5 | Bathroom and kitchen sockets | 16 A | 2.5 mm² |
| C9 | Air conditioning | 25 A | 6 mm² |
Basic electrification: 5,750 W, minimum two RCDs. Elevated electrification: 9,200 W, minimum three RCDs; applies for example with air conditioning, electric heating or larger homes.